Vanceboro

The Division of Water Resources (DWR) provides the data contained within this Local Water Supply Plan (LWSP) as a courtesy and service to our customers. DWR staff does not field verify data. Neither DWR, nor any other party involved in the preparation of this LWSP attests that the data is completely free of errors and omissions. Furthermore, data users are cautioned that LWSPs labeled PROVISIONAL have yet to be reviewed by DWR staff. Subsequent review may result in significant revision. Questions regarding the accuracy or limitations of usage of this data should be directed to the water system and/or DWR.

1. System Information

Contact Information

Complete

Water System Name: Vanceboro   PWSID: 04-25-020
Mailing Address:PO Box 306
Vanceboro, NC 28586
Ownership:Municipality
 
Contact Person:Beverly W. DrakeTitle:Town Clerk
Phone:252-244-0919Cell/Mobile:--
 
Secondary Contact:Mike Houston Phone:919-812-6088
Mailing Address:
, NC
Cell/Mobile:--
Distribution System
Line Type Size Range (Inches) Estimated % of lines
Asbestos Cement 8 5.00 %
Polyvinyl Chloride 2-6 95.00 %
What are the estimated total miles of distribution system lines?   16 Miles
How many feet of distribution lines were replaced during 2024?   0 Feet
How many feet of new water mains were added during 2024?   0 Feet
How many meters were replaced in 2024?   18
How old are the oldest meters in this system?   56 Year(s)
How many meters for outdoor water use, such as irrigation, are not billed for sewer services?   0
What is this system's finished water storage capacity?   0.5500 Million Gallons
Has water pressure been inadequate in any part of the system since last update? Line breaks that were repaired quickly should not be included.   No
Programs
Does this system have a program to work or flush hydrants?   Yes, As Needed
Does this system have a valve exercise program?   No
Does this system have a cross-connection program?   No
Does this system have a program to replace meters?   Yes
Does this system have a plumbing retrofit program?   No
Does this system have an active water conservation public education program?   Yes
Does this system have a leak detection program?   Yes

Employees look for leaks while in the field and utilize NCRWA as needed.

Water Conservation
What type of rate structure is used?   Increasing Block
How much reclaimed water does this system use?   0.0000 MGD   For how many connections?   0
Does this system have an interconnection with another system capable of providing water in an emergency?   Yes

2. Water Use Information

Service Area
Sub-Basin(s)% of Service Population
Neuse River (10-1)100 %
County(s)% of Service Population
Craven100 %
What was the year-round population served in 2024?   1,864
Has this system acquired another system since last report?   No
Water Use by Type
Type of Use Metered
Connections
Metered
Average Use (MGD)
Non-Metered
Connections
Non-Metered
Estimated Use (MGD)
Residential 494 0.1170 0 0.0000
Commercial 0 0.0000 0 0.0000
Industrial 0 0.0000 0 0.0000
Institutional 1 0.0600 0 0.0000

How much water was used for system processes (backwash, line cleaning, flushing, etc.)?   0.0150 MGD

Water Sales
Purchaser PWSID Average
Daily Sold
(MGD)
Days
Used
Contract Required to
comply with water
use restrictions?
Pipe Size(s)
(Inches)
Use
Type
MGD Expiration Recurring
Craven County 04-25-055 0.0000 0 Yes Yes Emergency

3. Water Supply Sources

Monthly Withdrawals & Purchases
Average Daily
Use (MGD)
Max Day
Use (MGD)
Average Daily
Use (MGD)
Max Day
Use (MGD)
Average Daily
Use (MGD)
Max Day
Use (MGD)
Jan 0.1311 May 0.2353 Sep 0.2158
Feb 0.2160 Jun 0.2235 Oct 0.2121
Mar 0.2164 Jul 0.2035 Nov 0.2139
Apr 0.2463 Aug 0.2122 Dec 0.2182

Ground Water Sources
Name or Number Average Daily Withdrawal (MGD) Max Day Withdrawal (MGD) 12-Hour Supply
(MGD)
CUA Reduction Year Offline Use Type
MGD Days Used
1 0.0940 366 0.2160 CUA0 Regular
2 0.1311 344 0.2160 CUA0 Regular
Ground Water Sources (continued)
Name or Number Well Depth (Feet) Casing Depth
(Feet)
Screen Depth (Feet) Well Diameter (Inches) Pump Intake Depth (Feet) Metered?
Top Bottom
1 165 128 160 6 108 Yes
2 165 128 160 6 108 Yes
Are ground water levels monitored?   Yes, Monthly
Does this system have a wellhead protection program?   Yes
Water Purchases From Other Systems
Seller PWSID Average
Daily Purchased
(MGD)
Days
Used
Contract Required to
comply with water
use restrictions?
Pipe Size(s)
(Inches)
Use
Type
MGD Expiration Recurring
Craven County 04-25-055 0.0000 0 Yes No 8 Emergency
Water Treatment Plants
Plant Name Permitted Capacity
(MGD)
Is Raw Water Metered? Is Finished Water Ouput Metered? Source
Vanceboro Water Plant 0.4320 Yes Yes Groundwater Castle Hayne
Did average daily water production exceed 80% of approved plant capacity for five consecutive days during 2024?  No
     If yes, was any water conservation implemented?  No
Did average daily water production exceed 90% of approved plant capacity for five consecutive days during 2024?  No
     If yes, was any water conservation implemented?  No
Are peak day demands expected to exceed the water treatment plant capacity in the next 10 years?  No

4. Wastewater Information

Monthly Discharges
Average Daily
Discharge (MGD)
Average Daily
Discharge (MGD)
Average Daily
Discharge (MGD)
Jan 0.1647 May 0.1743 Sep 0.1921
Feb 0.1345 Jun 0.1121 Oct 0.2094
Mar 0.2193 Jul 0.1674 Nov 0.1235
Apr 0.1376 Aug 0.2291 Dec 0.1260

How many sewer connections does this system have?   481
How many water service connections with septic systems does this system have?   2
Are there plans to build or expand wastewater treatment facilities in the next 10 years?   No
Wastewater Permits
Permit Number Type Permitted Capacity
(MGD)
Design Capacity
(MGD)
Average Annual
Daily Discharge
(MGD)
Maximum Day Discharge
(MGD)
Receiving Stream Receiving Basin
NC0031828 WWTP 0.3000 0.3000 0.1658 0.9000 Swift Creek Neuse River (10-1)
NC0080071 WTP 0.0000 0.0000 0.0010 0.0000 Maul Swamp Neuse River (10-1)

5. Planning

Projections
  2024 2030 2040 2050 2060 2070
Year-Round Population 1,864 1,875 1,894 1,911 1,928 1,946
Seasonal Population 0 0 0 0 0 0
 
Residential 0.1170 0.1177 0.1188 0.1198 0.1208 0.1218
Commercial 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Industrial 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Institutional 0.0600 0.0603 0.0609 0.0614 0.0620 0.0624
System Process 0.0150 0.0150 0.0151 0.0152 0.0153 0.0154
Unaccounted-for 0.0252 0.0253 0.0256 0.0258 0.0260 0.0262
Demand v/s Percent of Supply
  2024 2030 2040 2050 2060 2070
Surface Water Supply 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Ground Water Supply 0.4320 0.4320 0.4320 0.4320 0.4320 0.4320
Purchases 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Future Supplies 0.0000 0.0000 0.0000 0.0000 0.0000
Total Available Supply (MGD) 0.4320 0.4320 0.4320 0.4320 0.4320 0.4320
Service Area Demand 0.2172 0.2183 0.2204 0.2222 0.2241 0.2258
Sales 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Future Sales 0.0000 0.0000 0.0000 0.0000 0.0000
Total Demand (MGD) 0.2172 0.2183 0.2204 0.2222 0.2241 0.2258
Demand as Percent of Supply 50% 51% 51% 51% 52% 52%

The purpose of the above chart is to show a general indication of how the long-term per capita water demand changes over time. The per capita water demand may actually be different than indicated due to seasonal populations and the accuracy of data submitted. Water systems that have calculated long-term per capita water demand based on a methodology that produces different results may submit their information in the notes field.

Your long-term water demand is 63 gallons per capita per day. What demand management practices do you plan to implement to reduce the per capita water demand (i.e. conduct regular water audits, implement a plumbing retrofit program, employ practices such as rainwater harvesting or reclaimed water)? If these practices are covered elsewhere in your plan, indicate where the practices are discussed here.    No Changes

Are there other demand management practices you will implement to reduce your future supply needs?   No Changes

What supplies other than the ones listed in future supplies are being considered to meet your future supply needs?   No Changes

How does the water system intend to implement the demand management and supply planning components above?   No Changes

Additional Information

Has this system participated in regional water supply or water use planning?  Yes, CCPCUA

What major water supply reports or studies were used for planning?  CCPCUA

Please describe any other needs or issues regarding your water supply sources, any water system deficiencies or needed improvements (storage, treatment, etc.) or your ability to meet present and future water needs. Include both quantity and quality considerations, as well as financial, technical, managerial, permitting, and compliance issues:   New radio read meters.

The Division of Water Resources (DWR) provides the data contained within this Local Water Supply Plan (LWSP) as a courtesy and service to our customers. DWR staff does not field verify data. Neither DWR, nor any other party involved in the preparation of this LWSP attests that the data is completely free of errors and omissions. Furthermore, data users are cautioned that LWSPs labeled PROVISIONAL have yet to be reviewed by DWR staff. Subsequent review may result in significant revision. Questions regarding the accuracy or limitations of usage of this data should be directed to the water system and/or DWR.